YASKAWA GA700 Technical Manual page 799

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
Be aware of the following points when manually setting V/f patterns.
• To set linear V/f characteristics at frequencies lower than that of E1-06, set E-07 = E1-09. In this case, the setting for E1-08 will be
disregarded.
• Ensure that the five frequencies are set according to the following rules to prevent triggering oPE10 [V/f Data Setting Error];
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
• Parameter E1-03 is not reset when the drive is initialized using A1-03.
E1-01: Input AC Supply Voltage
No.
Name
(Hex.)
E1-01
Input AC Supply
Voltage
(0300)
NOTICE: Set this parameter to align with the drive input voltage (not motor voltage). The protective features of the drive will not
function if this parameter is incorrect. Failure to obey will cause incorrect drive operation.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value used for the motor protective functions in
drive, the detection level changes for some motor protective functions.
Voltage
E1-01 Setting
200 V class
All settings
Setting value ≥
400 V
400 V class
Setting value <
400 V
*1
This is the protection function enabled in drives with built-in braking transistors. These values show the level that will trigger the
built-in braking transistor. Refer to "YASKAWA AC Drive 72060001 Series Option Braking Unit and Braking Resistor Unit
Installation Manual (TOBPC72060001)" for more information.
E1-03: V/f Pattern Selection
No.
Name
(Hex.)
E1-03
V/f Pattern Selection
(0302)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Figure 11.74 V/f Pattern
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive input voltage.
Table 11.48 Values Related to the Drive Input Voltage
BTR Operation
Level
ov Detection
Level
(rr Detection
Level)
410 V
394 V
820 V
788 V
820 V
788 V
V/f
CL-V/f
OLV
CLV
AOLV
Sets the V/f pattern for the drive and motor. You can use one of the preset
patterns or you can make a custom pattern.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Table
Approximate Values
L2-05
[Undervoltage
Detection Lvl
(Uv1)]
*1
190 V
380 V
350 V
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.6 E: Motor Parameters
Default
(Range)
200 V Class: 230 V,
400 V: 400 V
(200 V Class: 155 to
255 V, 400 V Class:
310 to 510 V)
11.48. With a 400 V class
L2-11
L3-17
[KEB DC Bus
[DC Bus
Voltage
Regulation
Setpoint]
Level]
260 V
375 V
500 V
750 V
460 V
750 V
Default
(Range)
F
(Determined by A1-
02)
11
799