10: Alarm
Setting
Function
10
Alarm
11: Fault Reset Command Active
Setting
Function
11
Fault Reset
Command Active
12: Timer Output
Setting
Function
12
Timer Output
Note:
Refer to "b4: Timer Function" for more information.
13: Speed Agree 2
Setting
Function
13
Speed Agree 2
Note:
• The motor rotation direction does not have an effect on the detection function. The drive uses the L4-01 value as the forward/reverse
detection level.
• CLV and CLV/PM control use motor speed as the reference.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
14: User-Set Speed Agree 2
Setting
Function
14
User-Set Speed
Agree 2
Note:
• The detection level configured with L4-03 is a signed value. The drive will only detect in one direction.
• CLV and CLV/PM control use motor speed as the reference.
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency
reference ± L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the in the range of frequency
reference ± L4-04.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive detects a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive receives the Reset command from the control circuit terminal,
serial communications, or the communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting when the drive uses the timer function as an output terminal.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04
[Speed Agree Detection Width (+/-)].
Figure 11.97 Speed Agree 2 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detect
Level (+/-)] ± L4-04 [Speed Agree Detect Width (+/-)] and in the range of the frequency reference
± L4-04.
11.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11