11.3 b: Application
b3-09: Speed Estimation ACR I Time
No.
Name
(Hex.)
b3-09
Speed Estimation
ACR I Time
(0199)
Expert
b3-10: Speed Estimation Detection Gain
No.
Name
(Hex.)
b3-10
Speed Estimation
Detection Gain
(019A)
Expert
If the drive detects ov [DC Bus Overvoltage] when you restart the motor, increase the setting value.
b3-14: Bi-directional Speed Search
No.
Name
(Hex.)
b3-14
Bi-directional Speed
Search
(019E)
0 : Disabled
The drive uses the frequency reference to detect the direction of motor rotation.
1 : Enabled
The drive detects the direction of motor rotation during Speed Search.
b3-17: Speed Est Retry Current Level
No.
Name
(Hex.)
b3-17
Speed Est Retry
Current Level
(01F0)
Expert
When a large quantity of current flows during Speed Estimation Speed Search, the drive temporarily stops
operation to prevent overvoltage and overcurrent. When the current is at the level set in b3-17, the drive tries
speed search again.
b3-18: Speed Est Retry Detection Time
No.
Name
(Hex.)
b3-18
Speed Est Retry
Detection Time
(01F1)
Expert
When the current is more than the level set in b3-17 [Speed Est Retry Current Level] during the time set in b3-18,
the drive tries speed search again.
b3-19: Speed Search Restart Attempts
No.
Name
(Hex.)
b3-19
Speed Search Restart
Attempts
(01F2)
718
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time for the automatic current regulator during Speed
Estimation Speed Search. Also adjusts speed search responsiveness. Usually
it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to correct estimated frequencies from Speed Estimation Speed
Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of Speed Search to the direction of the frequency
reference or in the motor rotation direction as detected by the drive.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level for the search retry function in Speed Estimation
Speed Search as a percentage where drive rated current is a setting value of
100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will wait to retry Speed Estimation
Speed Search when too much current flow stopped the Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times to restart Speed Search if Speed Search does not
complete.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
Determined by A1-02
(0.0 - 1000.0 ms)
Default
(Range)
1.05
(1.00 - 1.20)
Default
(Range)
Determined by A1-02
(0, 1)
Default
(Range)
150%
(0 - 200%)
Default
(Range)
0.10 s
(0.00 - 1.00 s)
Default
(Range)
3 times
(0 - 10 times)