YASKAWA GA700 Technical Manual page 107

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Termi
Mode
nals
Master frequency reference pulse
train input
RP
(Master frequency reference)
+V
Power supply for frequency setting 10.5 V (allowable current 20 mA maximum)
-V
Power supply for frequency setting -10.5 V (allowable current 20 mA maximum)
MFAI1
A1
(Master frequency reference)
MFAI2
A2
Master
(Combined to terminal A1)
Frequency
Reference
MFAI3/PTC input
A3
(Auxiliary frequency reference)
AC
Frequency reference common
E (G)
Connecting shielded cable
Output Terminals
Refer to
Table 2.21
and
Table 2.22
Type
Terminal
N.O. output
MA
(Fault)
Fault Relay
N.C. output
Output
MB
(Fault)
MC
Digital output common
M1
MFDO
(During run)
M2
M3
MFDO
MFDO
(Zero speed)
M4
M5
MFDO
(Speed agree 1)
M6
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Name (Default)
• Response frequency: 0 Hz to 32 kHz
• H level duty: 30% to 70%
• H level voltage: 3.5 V to 13.2 V
• L level voltage: 0.0 V to 0.8 V
• Input impedance: 3 kΩ
Voltage input or current input
Select terminal A1 with DIP switch S1-1 and H3-01 [Terminal A1 Signal
Level Select].
Select terminal A2 with DIP switch S1-2 and H3-09 [Terminal A2 Signal
Level Select]
• -10 V to +10 V/-100% to +100%
• 0 V to 10 V/100% (input impedance: 20 kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
• Voltage input or current input
Select using DIP switch S1-3 and H3-05 [Terminal A3 Signal Level
Select].
– -10 V to +10 V/-100% to +100%
– 0 V to 10 V/100% (input impedance: 20 kΩ)
– 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
• PTC input (Motor Overheat Protection)
Set DIP switch S4 to "PTC" and set DIP switch S1-3 to "V" to set terminal
A3 for PTC input.
0 V
for a list of output terminals and functions.
Table 2.21 Control Circuit Output Terminals
Name (Default)
• Relay output
• 30 Vdc, 10 mA to 1 A
• 250 Vac, 10 mA to 1 A
• Minimum load: 5 V, 10 mA (Reference value)
• Relay output
• 30 Vdc, 10 mA to 1 A
• 250 Vac, 10 mA to 1 A
• Minimum load: 5 V, 10 mA (Reference value)
Function (Signal Level)
Function (Signal Level)
Note:
Do not set functions that frequently switch ON/OFF to MFDO (M1 to
M6) because this will decrease the performance life of the relay
contacts. Yaskawa estimates switching life at 200,000 times (assumes 1
A, resistive load).
2.14 Control Circuit Wiring
-
2
107