11.2 A: Initialization Parameters
A1-12: Bluetooth ID
No.
Name
(Hex.)
A1-12
Bluetooth ID
(1564)

A2: User Parameters

You can register frequently used parameters and recently changed parameters here to access them quickly. You
can show the registered parameters in [User Custom Parameters] in the main menu.
A2-01 to A2-32: User Parameters 1 to 32
No.
Name
(Hex.)
A2-01 to A2-
User Parameters 1 to
32
32
(0106 - 0125)
Note:
• Settings for A2-01 to A2-32 change when the A1-06 [Application Preset] value changes.
• You must set A1-01 = 1 [Access Level Selection = User Parameters] to access parameters A2-01 to A2-32.
• When A1-07 = 1 or 2 [DriveWorksEZ Function Selection = DWEZ Enabled or Enabled/Disabled wDigital Input], the drive saves qx-
xx [DriveWorksEZ Parameters] to A2-01 to A2-32.
The drive saves these parameters to A2-01 to A2-32.
• The drive saves a maximum of 32 parameters.
Note:
Set A1-01 = 2 [Advanced Level] or A1-01 = 3 [Expert Level] to register the necessary parameters.
• The drive automatically saves changed parameters to A2-17 to A2-32.
Note:
Set A2-33 = 1 [User Parameter Auto Selection = Enabled].
A2-33: User Parameter Auto Selection
No.
Name
(Hex.)
A2-33
User Parameter Auto
Selection
(0126)
0 : Disabled: Manual Entry Required
Set User Parameters manually.
1 : Enabled: Auto Save Recent Parms
The drive automatically registers changed parameters to A2-17 to A2-32. The drive automatically saves the most
recently changed parameter to A2-17, and saves a maximum of 16 parameters. After the drive registers 16
parameters, when you save a new parameter, the drive will remove a parameter from the User Parameter list to
make space for the new parameter. The drive removes parameters with First In, First Out.
You can show the registered parameters in [User Custom Parameters] in the main menu.
Note:
In General-Purpose Setup Mode, the drive registers parameters starting from A2-27 because parameters A2-26 and lower are already
registered by default.
696
V/f
CL-V/f
OLV
CLV
AOLV
Sets the password necessary to use Bluetooth to control the drive with a
mobile device.
V/f
CL-V/f
OLV
CLV
AOLV
You can select a maximum of 32 parameters for the drive and set them to
parameters A2-01 to A2-32. The [User Parameters] section of the keypad
main menu shows the set parameters. You can immediately access these set
parameters.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the automatic save feature for changes to parameters A2-17 to A2-32
[User Parameters 17 to 32].
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
-
(0000 - 9999)
Default
(Range)
Parameters in
General-Purpose
Setup Mode
(Determined by A1-
07)
Default
(Range)
Determined by A1-06
(0, 1)