N2: Spdfeedbackdetectcontrol(Afr)Tun; N3: High Slip Braking (Hsb) - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.12 n: Special Adjustment

n2: SpdFeedbackDetectControl(AFR)Tun

No.
Name
(Hex.)
n2-01
Automatic Freq
Regulator Gain
(0584)
n2-02
Automatic Freq
Regulator Time 1
(0585)
n2-03
Automatic Freq
Regulator Time 2
(0586)

n3: High Slip Braking (HSB)

No.
Name
(Hex.)
n3-01
HSB Deceleration
Frequency Width
(0588)
Expert
n3-02
HSB Current Limit
Level
(0589)
Expert
n3-03
HSB Dwell Time
at Stop
(058A)
Expert
n3-04
HSB Overload
Time
(058B)
Expert
n3-13
OverexcitationBrak
ing (OEB) Gain
(0531)
n3-14
OEB High
Frequency
(0532)
Injection
Expert
n3-21
HSB Current
Suppression Level Sets the upper limit of the current that is suppressed at the time of
(0579)
n3-23
Overexcitation
Braking Operation Sets the direction of motor rotation where the drive will enable
(057B)
580
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the AFR function as a magnification value. Usually
it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the rate of change for the AFR
function. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the speed difference of the AFR
function. Use this parameter for speed searches or regeneration.
Usually it is not necessary to change this setting.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets how much the drive lowers the output frequency during high-
slip braking as a percentage where E1-04 [Maximum Output
Frequency] = 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum current output during high-slip braking as a
percentage where E2-01 [Motor Rated Current (FLA)] = 100%.
Also set the current suppression to prevent exceeding drive overload
tolerance.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the dwell time, a length of time when high-slip braking is
ending and during which the motor speed decreases and runs at a
stable speed. For a set length of time, the drive will hold the actual
output frequency at the minimum output frequency set in E1-09.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time used to detect oL7 [High Slip Braking Overload],
which occurs when the output frequency does not change during
high-slip braking. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain value that the drive multiplies by the V/f pattern output
value during overexcitation deceleration to calculate the
overexcitation level.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that injects harmonic signals during overexcitation
deceleration.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
overexcitation deceleration, where the drive rated current = 100%
value.
V/f
CL-V/f
OLV
CLV
AOLV
overexcitation.
0 : Disabled
1 : Enabled Only when Rotating FWD
2 : Enabled Only when Rotating REV
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
1.00
989
(0.00 - 10.00)
50 ms
989
(0 - 2000 ms)
750 ms
990
(0 - 2000 ms)
Default
Ref.
(Range)
5%
992
(1 - 20%)
Determined by C6-
992
01, L8-38
(0 - 200%)
1.0 s
992
(0.0 - 10.0 s)
40 s
992
(30 - 1200 s)
1.10
992
(1.00 - 1.40)
0
993
(0, 1)
100%
993
(0 - 150%)
0
993
(0 - 2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents