YASKAWA GA700 Technical Manual page 608

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.17 U: Monitors
No.
Name
(Hex.)
U4-21
Run Command
Source
(07DD)
U4-22
Modbus CmdData
(hex)
(07DE)
608
Description
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected Run command source.
The keypad shows the Run command source as "XY-nn" as specified
by these rules:
X: External Reference 1/2 Selection [H1-xx = 2] selection status
• 1: b1-02 [Run Command Selection 1]
• 2: b1-16 [Run Command Selection 2]
Y: Run command source
• 0: Keypad
• 1: Control circuit terminal
• 3: MEMOBUS/Modbus communications
• 4: Communication option card
• 7: DriveWorksEZ
nn: Run command limit status data
• 00: No limit status.
• 01: The Run command was left ON when the drive stopped in the
Programming Mode.
• 02: The Run command was left ON when switching from
LOCAL Mode to REMOTE Mode.
• 03: The Run command is in standby after the drive was energized
until the soft charge bypass contactor turns ON.
Note:
The drive will detect Uv1 [DC Bus Undervoltage] or Uv
[Undervoltage] if the soft charge bypass contactor does not turn
ON after 10 s.
• 04: Restart after run stop is prohibited.
• 05: Fast stop has been executed using the MFDI terminal. Or, the
motor has ramped to stop by pressing the STOP key on the
keypad.
• 06: b1-17 = 0 [Run Command at Power Up = Disregard Existing
RUN Command] is set.
• 07: During baseblock while coast to stop with timer.
• 08: Frequency reference is below E1-09 [Minimum Output
Frequency] during baseblock.
• 09: Waiting for the Enter command from PLC.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the operation signal (register 0001H) sent to the drive from
MEMOBUS/Modbus communications as a 4-digit hexadecimal
number (zero suppress). The keypad shows the operation signal as
specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Multi-function input 8
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
MFAO Signal
Ref.
Level
No signal output
-
The keypad shows
the Run command
source as "XY-nn"
as specified by
these rules:
available
No signal output
-
available