Input/Output - YASKAWA MOTIONPACK-110 Descriptive Information

Motion controller for fa/fms for up to 3-axis drive
Table of Contents

Advertisement

9.1.2.3
Power Supply for Input/Output
Signals
A 24 VDC power
unit is necessary
for input/output
signals.
A power
unit meeting
the speci-
fications of Table 9.4 should be provided.
Table
9.4
Specifications
for
24 VDC
Power
Supply
Item
Specifications
Input Voltage
100/110 VAC, 50/60 Hz
Rated Voltage
24 V
Rated Current
2 A (3-axis system)
Output Stability
Less than -+10 %
Ripple Noise
Less than 300mVp-p
Leak Current
Less than 0.5 mA
Overcurrent
Protection
Provided
Working Temperature
0 to +55°C
Storing Temperature
-20°C to +85°C
Relative
Humidity
30 to 90% (non-condensing)
Input,
, Frame
Withstand
voltage:
1,500 VAC,
1 minute
Insulation
Input ------Output
Resistance:
More than 100 MD at 500 VDC
Output,
, Frame
,din
Example o fmodel:
Type:
BY242R5
Manufacturer:
Shindengen
Kogyo
KK
Input:
85 to 115 VAC,
47 to 440 Hz
OutPut!
24 V, 2.5 A
9.2
INPUT/OUTPUT
AT
MACHINE
SIDE
9.2,1
RULES
FOR INPUT/OUTPUT
SIGNALS
9.2.1.1
Rules for Input Signals
Input
signals
referred
to herein
are those
sent from
the machine
side to Motionpack-ll0.
For connection,
0V common
method
(True-Low
method)
shown
in Fig.
9.3 is applied.
Effective
condition
of the input
voltage
is as follows.
(1) ON or OFF
input
signals
with
a duration
longer
than
50 ms are effective.
ON
I
I
J
I
50 msORMORE
50 msORMORE ,
Fig. 9.2
168

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents