19.7

Setting of Connected Equipment for GOT

The setting for connection to the SLC500/MicroLogix Series PLC can be executed using the GOT-F900
and the screen creation software (GT Designer2, GT Designer or DU/WIN).
1) GOT-F900 Series
When the main menu screen change operation is disabled.
a)While pressing and holding the upper left corner of the screen,
turn on the power. Keep holding the upper left corner for about
25 seconds more.
Then, press "END" at the upper right corner.
b)Press "PLC TYPE".
c) Set the following.
PLC TYPE: AB SLC500
AB Micrologix
CONNECTION:CPU PORT (RS-232C)
DST STATION # (STATION #) : 00 to 31
GOT STATION # (−)
When the main menu screen change operation is enabled.
a)Press the upper left corner of the screen. (The position to be
pressed can be changed in the GOT and the screen creation
software.)
b)Press "OTHER MODE" on the menu.
c) Press "SET-UP MODE" on the menu.
d)Press "PLC TYPE".
e)Set the following.
PLC TYPE: AB SLC500
AB Micrologix
CONNECTION:CPU PORT (RS-232C)
DST STATION # (STATION #) : 00 to 31
GOT STATION # (−)
- When the screen data is transferred to the GOT-F900, the old data including the PLC type, connection type,
and station number are overwritten.
- The "PLC type" selection item display varies depending on the OS version.
"PLC TYPE" selection item display
F940WGOT
F940GOT, Handy GOT
Version
F930GOT
F930GOT-K
F920GOT-K (24V)
*1 The selection item display is changed to "AB SLC500" and "AB MicroLogix".
Connection of SLC500/MicroLogix Series PLC (Manufactured by Allen-Bradley) 19
Operation
: −
Operation
: −
Display (screen name)
The "LANGUAGE" screen appears.
The "SET-UP MODE" screen appears.
The "PLC TYPE" screen appears.
Display (screen name)
The "SELECT MODE" screen appears.
The "OTHER MODE" screen appears.
The "SET-UP MODE" screen appears.
The "PLC TYPE" screen appears.
AB SLC500
2.00 or later
2.00 or later
4.60 or later
1.20 or later
11
12
13
14
15
16
17
*1
AB SLC500
AB MicroLogix
1.00 or later
18
6.00 or later
6.00 or later
4.60 or later
1.20 or later
19
20
19-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents