Mitsubishi Electric F920GOT-K Hardware Manual page 67

Got-f900 series graphic operation terminal
Table of Contents

Advertisement

GOT-F900 SERIES (CONNECTION)
F930GOT
F930GOT-BWD-E
F920GOT-BBD-K-E
80mA/24V DC
200mA/24V DC
(70mA/24V DC)
Built-in (irreplaceable)
Operation continues against power failure of
5ms or less.
FX2NC-32BL
(life: Approx. 3 years)
0~50 ° C
In conformance
to JIS B3502
and IEC 61131-2
In conformance to JIS B3502 and IEC 61131-2 (147 m/s 2 , 3 times in each of X, Y and Z directions)
By noise simulator of 1,000 Vp-p in noise voltage, 1 µs in noise width and 30 to 100 Hz in frequency
5 MΩ or more by 500V DC megger
Grounding resistance
100Ω or less
*6*7
Equivalent to IP65f
50,000 hours
or more
*1 When the power is turned on, the current consumption of 750 mA/24V DC maximum is applied.
*2 0 to 50 × C when the screen is installed laterally. 0 to 40 × C when the screen is installed longitudinally or horizontally.
*3 0 to 40 × C when the extension interface is used.
*4 The life of the backlight above indicates the value at 25 × C.
*5 Between all power terminals of the PLC and ground terminal.
*6 The relevancy is confirmed in the test for IP65f or IP54. However, this test result does not provide any guarantees that
the product stands against use in all sorts of environment.
*7 As regarding the front panel
F920GOT-K
F920GOT-BBD5-K-E
5V DC
Supplied from PLC
220mA/5V DC
(180mA/5V DC)
0~50 ° C
35 to 85%RH (no condensation)
Free from corrosive gas and much dusts
Frequency
10~57Hz
With intermittent
vibration
57~150Hz
10~57Hz
With continuous
vibration
57~150Hz
*5
500V AC for 1 min
*5
*6*7
Equivalent to IP65f
Approx. 50,000 hours or more (working temperature: 25 ° C)
Guarantee period is 1 year.
LED (Red/White)
Handy GOT
F940GOT-SBD-(R)H-E
24V DC+10%-15%
(separately prepared DC power supply)
300mA/24V DC
(200mA/24V DC)
Built-in (irreplaceable)
Operation continues against power failure of 5ms or less.
FX2NC-32BL
(life: Approx. 3 years)
0~40 ° C
Acceleration Amplitude
10 times in each
0.075mm
of X, Y and Z
2
9.8m/s
0.035mm
2
4.9m/s
500V AC for 1 min
(between all power terminals and ground terminal)
5 MΩ or more by 500V DC megger
(between all power terminals and ground terminal)
Grounding resistance 100Ω or less
Equivalent to IP54 *6
40,000 hours or more
Cold cathode tube (working temperature: 25 ° C)
Guarantee period is 1 year.
Specifications 3
F940GOT-LBD-(R)H-E
directions
(for 80 min)
3-29
1
2
3
4
5
6
7
8
9
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents