Batch Write Command - Mitsubishi Electric F920GOT-K Hardware Manual

Got-f900 series graphic operation terminal
Table of Contents

Advertisement

GOT-F900 SERIES (CONNECTION)
14.6.2

Batch Write Command

The contents of the batch write command are explained below as an example of the format 2.
1 byte
1 byte 4 bytes
STX
Address
1
(02H)
(31H)
Use Example
When "64H" and "65H" are written respectively to virtual devices D100 and D101 of the GOT-F900.
STX
Address
1
0
0
C
(02H)
(31H)
30H
30H 43H 38H 30H 34H
Before execution
520 bytes maximum
2 bytes
Number
Data 1
Data 2
Data 3
of points
(1 to 64)
Sum check range
Execution
is normally
terminated
.
ACX
(06H)
Number
D100
of points
8
0
4
0
0
6
4
0
30H
30H 36H 34H 30H 30H 36H 35H
Execution
is normally
terminated.
ACX
(06H)
D100
0000H
D101
0000H
D102
0000H
Connection of Microcomputer 14
2 x (1 to 255) bytes
Data 4
Data n-1
. . . . .
Error has
occurred.
NAK
(15H)
Sum
D101
ETX
check
Transmitted from
the host to the GOT.
0
6
5
0
8
(03H)
30H 38H
Transmitted from the
GOT to the host.
D100 0064H
D101 0065H
D102 0000H
After execution
1 byte
2 byte
Data n
ETX
Sum
check
(03H)
14-19
11
12
13
14
15
16
17
18
19
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents