GOT-F900 SERIES (CONNECTION)
20.3
Setting in SIMATIC S7-200
When connecting the SIMATIC S7-200 Series PLC, the communication specifications of the RS-232C
port should be set using the peripheral equipment for the SIMATIC S7-200 Series (STEP7-Micro/WIN).
20.3.1
Communication Setting Specifications
Set the baud rate, highest address, etc. of the SIMATIC S7-200 Series PLC.
1) Setting in the PLC
Set the following items using the programming software for the SIMATIC S7-200 Series (STEP7-
Micro/WIN32).
PLC Address
Highest Address
Baud Rate
Retry Count
Gap Update Factor
Procedure
a) Open STEP7-Micro/WIN32 software.
b) From the menu on the tool bar, select "View"-"Communications".
Set "Remote Address" to the destination PLC station number (The default value is "2".)
c) From the menu on the tool bar, select "View"-"System Block".
Set "PLC Address" to a value in the range from 1 to 31, "Highest Address" to "31", "Baud Rate" to
"19.2 kbps", "Retry Count" to "3", and "Gap Update Factor" to "10".
Click the [OK] button.
d) Transfer the program to the PLC.
Connection of SIMATIC S7-200/300/400 Series PLC (Manufactured by Siemens AG) 20
Item
Set value
1 to 31
31
19200 bps
3
10
20-6