3) In the case of CPM1A Series (CPU equipped with built-in peripheral port)
In the CPU CPM1A-10CDR-A, write data to the data memory (DM) shown in the table below using a
peripheral tool.
The table below explains the data memory (DM) Nos. and set values which should be set using a
peripheral tool.
Setting item
Communication
Transmission speed
Transmission delay time
Unit number
4) In the case of CPM2A Series (CPU equipped with built-in RS-232C port)
In the CPU CPM2A-30CDR-A, write data to the data memory (DM) shown in the table below using a
peripheral tool. In the CPU CPM2A-30CDR-A, set the DIP switch shown below.
Setting item
CPM2A-30CDR-A
Communication condition setting
switch
The table below explains the data memory (DM) Nos. and set values which should be set using a
peripheral tool.
Setting item
Communication
Transmission speed
Transmission delay time
Unit number
Connection of SYSMAC C Series PLC (Manufactured by Omron) 15
Port
Set value (hexadecimal)
DM6650
0001H
DM6651
0304H
DM6652
0000H
DM6653
0000 to 0031
Set value
OFF
Port
Set value (hexadecimal)
DM6645
0001H
DM6646
0304H
DM6647
0000H
DM6648
0000 to 0031
Remarks
Communication condition: Set individually
(in accordance with setting of DM6651)
Host link mode
Baud rate: 19200 bps
Start bit length: 1 bit
Data length: 7 bits
Stop bit length: 2 bits
Parity: Even
Transmission delay time: 0ms
Host link unit number (BCD value)
Remarks
Remarks
Communication condition: Set individually
(in accordance with setting of DM6646)
Host link mode
CTS control: Not provided
Baud rate: 19200 bps
Start bit length: 1 bit
Data length: 7 bits
Stop bit length: 2 bits
Parity: Even
Transmission delay time: 0ms
Host link unit number (BCD value)
15-15
11
12
13
14
15
16
17
18
19
20