GOT-F900 SERIES (CONNECTION)
18.3

Setting of Series

When connecting the control unit or the CPU unit, the following setting should be executed using the
Programming tool for the FP Series. When connecting the computer communication unit, the following
setting should be executed using the DIP switches.
Further information for method of setting operation can be in relevant manual FP Series.
18.3.1

Communication Setting Specifications

This section explains the setting in the FP Series.
1) Setting the transmission specifications
Set the transmission specifications as shown in the table below in the FP0/FPΣ Series control unit
and the FP2SH Series CPU unit using the peripheral equipment for the FP Series or in the computer
communication unit using the DIP switches.
For the DIP switch setting method, refer to the manual of the computer communication unit.
Transmission speed
Data format
-
The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be
changed.
2) Setting the station number
Align the station number to the value (01 to 31) set in the GOT-F900.
If "00" is set in the GOT-F900, it is treated as "01".
The sample screens above are in Japanese.
Connection of FP Series PLC (Manufactured by Matsushita Electric Works) 18
Item
CPU direct connection
Data length
Parity check
Stop bit
Start code
STX not provided
End code
19200bps
7 bits
Provided (even)
Fixed in the FP2-CCU
1 bit
Fixed in the FP2-CCU
Fixed in the FP2-CCU
CR
Fixed in the FP2-CCU
Remarks
18-5
11
12
13
14
15
16
17
18
19
20