Mitsubishi Electric F920GOT-K Hardware Manual page 521

Got-f900 series graphic operation terminal
Table of Contents

Advertisement

GOT-F900 SERIES (CONNECTION)
2) Software
In the personal computer connected
to the GOT-F900, screen data cannot
Screen
be transferred.
creation
Communication with the screen
software
creation software is disabled. An
error message is displayed.
Connection of SLC500/MicroLogix Series PLC (Manufactured by Allen-Bradley) 19
Contents of trouble
Check points and countermeasures
A SLC500/MicroLogix Series PLC, bar code reader or printer
is connected.
• Causes
The RS-232C connector to which the personal computer is
connected is set to be used for another piece of equipment.
• Countermeasures
In the GOT-F900, select by hand "SELECT MODE"-"OTHER
MODE"-"DATA TRANSFER".
Or set a bar code reader to invalid and a printer to "DON'T
USE".
Something is wrong with the cable between the GOT-F900
and the personal computer.
• Causes
The wrong cable is used or the connection is bad.
• Countermeasures
Check the cable.
11
12
13
14
15
16
17
18
19
20
19-21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents