Troubleshooting - Mitsubishi Electric F920GOT-K Hardware Manual

Got-f900 series graphic operation terminal
Table of Contents

Advertisement

GOT-F900 SERIES (CONNECTION)
6.6

Troubleshooting

For reference, this section summarizes frequently asked questions about connection of the GOT-F900
to a personal computer.
1) GOT-F900
Classification
When the screen data is transferred by
GT Designer
the screen creation software, "No
DU/WIN
response from terminal", etc. is
displayed.
When the screen data is transferred by
the screen creation software, the
GOT-F900
"DATA TRANSFER" screen does not
appear in the GOT-F900.
Contents of trouble
Connection of Peripheral Equipment 6
Check points and countermeasures
The RS-232C port of the GOT-F900 is used by another
connected equipment (bar code reader or printer).
• Causes
1)"RS-232C" is specified for PLC connection.
2)The bar code reader is set valid.
3)The printer is set valid.
Confirm the settings above in the screen creation
software.
• Countermeasures
Select by hand the data transfer mode in the GOT-F900.
Start up the system screen, display the "SELECT
MODE" screen, select "OTHER MODE" - "DATA
TRANSFER" on the menu, then transfer the screen data.
1
2
3
4
5
6
7
8
9
10
6-13