Setting Examples in SYSMAC
When connecting the GOT-F900 to the SYSMAC
shown below should be written to data memory (DM) using a peripheral tool.
This paragraph explains the contents of data memory (DM) to be set in each unit.
1) In the case of SYSMAC
In the CPU C200HX-CPU44-Z, set the DIP switch shown below.
C200HX-CPU44-Z
DIP switch SW5
The table below explains the data memory (DM) Nos. and set values which should be set using a
peripheral tool.
Setting item
Communication
Transmission speed
Transmission delay time
Unit number
2) In the case of SYSMAC
When connecting the GOT-F900 to the port 1 or the port 2 in the C200HW-COM06-V1, set the DIP
switch shown below.
C200HW-COM06-V1
DIP switch SW1, 2
The table below explains the data memory (DM) Nos. and set values which should be set using a
peripheral tool.
Setting item
Communication
Transmission speed
Transmission delay time
Unit number
Connection of SYSMAC C Series PLC (Manufactured by Omron) 15
α α α α
Series (CPU equipped with built-in RS-232C port)
Setting item
Port
DM6645
DM6646
DM6647
DM6648
α α α α
Series (serial communication board)
Setting item
Setting item
Port B
DM6550 DM6555
DM6551 DM6556
DM6552 DM6557
DM6553 DM6558
α α α α
(C200HE/HG/HX)/CPM 1A/2A/2C Series
α
(C200HE/HG/HX) or CPM 1A/2A/2C Series, the data
Set value
OFF
Set value (hexadecimal)
0001H
0304H
0000H
0000 to 0031
Set value
4-wire type
(without terminal resistor)
Set value
(hexadecimal)
Port A
0001H
0304H
0000H
0000 to 0031
Remarks
Remarks
Communication condition: Set individually
(in accordance with setting of DM6646)
Host link mode
CTS control: Not provided
Baud rate: 19200 bps
Start bit length: 1 bit
Data length: 7 bits
Stop bit length: 2 bits
Parity: Even
Transmission delay time: 0ms
Host link unit number (BCD value)
Remarks
Refer to the description on the switches of
the C200HW-COM06-V1.
DIP switch SW1: 4
DIP switch SW2: OFF
Remarks
Communication condition: Set individually
(in accordance with setting of next DM)
Host link mode
CTS control: Not provided
Baud rate: 19200 bps
Start bit length: 1 bit
Data length: 7 bits
Stop bit length: 2 bits
Parity: Even
Transmission delay time: 0ms
Host link unit number (BCD value)