Error messages during commissioning (SF...)

After completion or during the parameter identification, error messages may be displayed.
Depending on the error code, the following instructions should be followed and the measures
indicated should be taken.
Code
SF000
No Error
The value entered for parameter
SF001
The value for parameter
SF002
Mech. Power
SF003
The value entered for parameter
The calculated slip frequency is negative. Check and, if necessary, correct the values for
SF004
parameters
Rated Speed
The calculated slip frequency is too high. Check and, if necessary, correct the values for
SF005
parameters
Rated Speed
The calculated total output of the drive is lower than the rated power. Check and, if
SF006
necessary, correct the value entered for parameter
SF007
The set configuration is not supported by the auto set-up routine.
SF011
The main inductance measurement has failed because the motor has a high slip. Correct
the rated motor values in parameters 370, 371, 372, 374, 375 and 376 . Carry out the
guided commissioning once again. In case an error message is displayed again, enter value
110 for
parameter Configuration
characteristic) if value 410 was set so far. Carry out the guided commissioning once again.
SF012
The leakage inductance measurement has failed because the motor has a high slip. Correct
the rated motor values in parameters 370, 371, 372, 374, 375 and 376 . Carry out the
guided commissioning once again. In case an error message is displayed again, enter value
110 for
parameter Configuration
characteristic) if value 410 was set so far. Carry out the guided commissioning once again.
SF021
The measurement of the stator resistance did not deliver a plausible value. Check the
cables at the terminals of the motor and the frequency inverter for proper connection and
check the contacts for corrosion and safe contact. Repeat the parameter identification
SF022
The measurement of the rotor resistance did not deliver a plausible value. Check the
cables at the terminals of the motor and the frequency inverter for proper connection and
check the contacts for corrosion and safe contact. Repeat the parameter identification
SF026
Setup aborted
9.2.10

Application data

Other parameters must be checked due to the great variety of drive applications and the resulting
parameter settings. The parameters queried during the guided commissioning procedure were
selected from standard applications. After completion of commissioning, further parameters can be
set in the PARA menu branch.
In the KP500 control unit, parameter numbers > 999 are shown in hexadecimal form
(999, A00 ... B5 ... C66).
108
Error messages
Measures / Remedy
Rated Current
Rated Current
376 and
Rated Voltage
372 and
Rated Frequency
372 and
Rated Frequency
30 (sensor-less control (SLC) according to V/f
30 (sensor-less control (SLC) according to V/f
Operating Instructions ACU
371 is too low. Correct the value.
371 is too high, referred to parameters
370. Correct the values.
375.
375.
Rated Mech. Power
Rated
376.
12/16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Active cube 501Active cube 401Active cube 601

Table of Contents