Product manual - IRT 710
3HKA00000186299-001 Revision: B
6.3.1 Updating revolution counters for axis calibration
Action
The calibration summary page for the selected mechanical unit is displayed.
Calibration method used at factory for each axis is shown, as well as calibration
method used during last field calibration.
Tap Calibration Methods on the right pane.
The calibration options are displayed.
Tap Revolution Counters.
In the Selection column select the axes for which revolution counters need to be up-
dated.
Tap Update.
A dialog box is displayed, warning that the updating operation cannot be undone:
Tap Update to proceed with updating the revolution counters.
Tap Cancel to cancel updating the revolution counters.
Tapping Update and a confirmation window is displayed.
Tap OK.
The revolution counter for the selected axes is updated.
CAUTION
If a revolution counter is incorrectly updated, it will cause incorrect track positioning,
which in turn may cause damage or injury!
Check the synchronization position very carefully after each update. See
the synchronization position on page
© Copyright 2023 ABB. All rights reserved.
359.
6 Calibration
Continued
Checking
343