(M) Monitor display and monitor output signal
5.11.10

Remote output function

The inverter output signals can be turned ON/OFF like the remote output terminals of a programma-
ble controller.
Pr.
495
M500
496
M501
497
M502
Remote output setting (REM signal, Pr. 496, Pr. 497)
● The output terminal can be turned ON/OFF with the Pr. 496 and Pr. 497 settings. ON/OFF control
can be performed for the remote output terminal via the PU connector, RS-485 terminals and
communication option.
● To assign the Remote output (REM) signal to the terminal to be used for remote output, set "96
(positive logic) or 196 (negative logic)" in any of Pr. 190 to Pr. 196 (output terminal function
selection).
● Refer to the fig. 5-178, and set "1" in the terminal bit (terminal with the REM signal assigned) of Pr.
496 or Pr. 497 to turn ON the output terminal (OFF when using negative logic). Set "0" to turn OFF
the output terminal (ON when using negative logic).
● For example, when Pr. 190 "RUN terminal function selection" = "96" (positive logic) and "1" (H01)
is set in Pr. 496, the terminal RUN turns ON.
Fig. 5-178:
Any value.
Y0 to Y6 are available when the extension output option (FR-A8AY) is installed.
RA1 to RA3 are available hen the relay output option (FR-A8AR) is installed.
5 - 380
Initial
Name
value
Remote output
0
selection
Remote output data 1
0
Remote output data 2
0
Pr. 496
Pr. 497
Remote output data
Setting
Description
range
Remote output data is cleared
0
when the power supply is turned
OFF
Remote output data is retained
1
when the power supply is turned
OFF
Remote output data is cleared
10
when the power supply is turned
OFF
Remote output data is retained
11
when the power supply is turned
OFF
Set values for the bits corresponding to each output terminal
0 to 4095
of the inverter output terminal. (Refer to the diagram below.)
Set values for the bits corresponding to each output terminal
0 to 4095
of options FR-A8AY and FR-A8AR. (Refer to the diagram
below.)
Parameters
Remote output data is
cleared during an
inverter reset
Remote output data is
retained during an
inverter reset
I001157E