Reset Selection/Disconnected Pu Detection/Pu Stop Selection - Mitsubishi Electric FR-A820-00046 Instruction Manual

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(E) Environment setting parameters
5.7.2

Reset selection/disconnected PU detection/PU stop selection

The reset input acceptance, disconnected PU (operation panel/parameter unit) connector detection
function and PU stop function can be selected.
Pr.
75
E100
E101
E102
E107
The parameters above will not return to their initial values even if parameter (all) clear is executed.
The setting range for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
The setting range for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Pr. 75 Setting
0, 100
1, 101
2, 102
3, 103
14 (Initial
value), 114
15, 115
16, 116
17, 117
Tab. 5-70:
Setting Pr. 75 = any of "100 to 103 and 114 to 117" will enable the reset limit function. The setting
is available for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
5 - 192
Name
Reset selection/disconnected
PU detection/PU stop selection
Reset selection
Disconnected PU detection
PU stop selection
Reset limit
Reset selection
Reset input always enabled
Reset input enabled only when
protective function activated
Reset input always enabled
Reset input enabled only when
protective function activated
Reset input always enabled
Reset input enabled only when
protective function activated
Reset input always enabled
Reset input enabled only when
protective function activated
Setting of parameter 75
Initial value
Setting range
0 to 3, 14 to 17
14
0 to 3, 14 to 17,
100 to 103, 114 to 117
0
0
1
0
0
1
0
1
1
0
0
1
Disconnected PU detection
Operation continues even when PU
is disconnected.
Inverter output shut off when PU
disconnected.
Operation continues even when PU
is disconnected.
Inverter output shut off when PU
disconnected.
Parameters
Description
For the initial setting, reset is always
enabled, without disconnected PU
detection, and with the PU stop
function.
Reset input is always enabled.
Reset input is enabled only when the
protective function is activated.
Operation continues even when the PU
is disconnected.
The inverter output is shut off when the
PU is disconnected.
Decelerates to a stop when the STOP
key is pressed in PU operation mode
only.
Decelerates to a stop when the STOP
key for PU is pressed in any of the PU,
external and communication operation
modes.
Reset limit disabled
Reset limit enabled
PU stop selection
Decelerates to a stop
when
is input in PU
operation mode only.
Decelerates to a stop
when
is input in any
of the PU, external and
communication operation
modes.