Protective functions
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
FR-A800
E.SAF
Safety circuit fault
The inverter trips when a safety circuit fault occurs.
The inverter trips if the either of the wire between S1 and SIC or S2 and SIC becomes non-
conductive while using the safety stop function.
When not using the safety stop function, the inverter trips when the shorting wire between
terminals S1 and PC or across S2 and PC is disconnected.
Check that the safety relay module or the connection has no fault when using the safety
stop function.
Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when
not using the safety stop function.
When using the safety stop function, check that wiring of terminal S1, S2 and SIC is correct
and the safety stop input signal source such as a safety relay module is operating properly.
Refer to the Safety stop function instruction manual for causes and countermeasures.
(Please contact your sales representative for the manual.)
When not using the safety stop function, short across terminals S1 and PC and across S2 and
PC with shorting wires. (Refer to page 2-54.)
E.PBT
E.13
Internal circuit fault
The inverter trips when an internal circuit fault occurs.
Please contact your sales representative.
E.OS
Overspeed occurrence
The inverter trips when the motor speed exceeds the Pr. 374 "Overspeed detection level" under
encoder feedback control, Real sensorless vector control, vector control, and PM sensorless
vector control. This protective function is not available in the initial status.
Check that the Pr. 374 setting is correct.
Check that the number of encoder pulses does not differ from the actual number of Pr.
369(Pr. 851) "Number of encoder pulses" (under encoder feedback control or vector control).
Set the Pr. 374 correctly.
Set the Pr 369 (851) correctly (under encoder feedback control or vector control).
Causes and corrective actions
FR-LU-08
Safety circuit fault
PBT fault
FR-LU-08
Intrnl circuit fault
Overspeed
FR-LU-08
occurrence
6 - 31