Parameters
Initializing the parameters required for the PM sensorless vector control (Pr. 998)
● PM parameter initialization sets parameters required for driving an IPM motor MM-CF.
● The offline auto tuning enables the operation with an IPM motor other than MM-CF and with SPM
motors.
● Two MM-CF IPM parameter initialization methods are available; setting Pr. 998 "PM parameter
initialization", and selecting
Pr.
998
E430
● To use a motor capacity that is one rank lower than the inverter capacity, set Pr. 80 "Motor capacity"
before performing IPM parameter initialization.
● When Pr. 998 = "3003, 8009, or 9009", the monitor is displayed and the frequency is set using the
motor rotations per minute. To use frequency to display or set, set Pr. 998 = "3103, 8109, or 9109".
● Set Pr. 998 = "0" to change the PM sensorless vector control parameter settings to the parameter
settings required to drive an induction motor.
● When using an IPM motor other than MM-CF, set Pr. 998 = "8009, 8109, 9009, or 9109". The setting
can be made after performing offline auto tuning.
FR-A800
Initial
Setting
Name
value
range
3003
3103
8009
PM parameter
0
initialization
8109
9009
9109
(IPM parameter initialization) mode on the operation panel.
Description
Parameter settings for an induction motor
0
(frequency)
For IPM motor MM-CF.
Parameter setting (rotations per minute)
For IPM motor MM-CF.
Parameter setting (frequency)
The parameters settings required to drive
an IPM motor other than MM-CF are set.
(rotations per minute) (after tuning)
The parameters settings required to drive
an IPM motor other than MM-CF are set.
(frequency) (after tuning)
The parameters settings required to drive
an SPM motor are set. (rotations per
minute) (after tuning)
The parameters settings required to drive
an SPM motor are set.
(frequency) (after tuning)
Control method
The parameter settings
required to drive an
induction motor are set.
The parameters settings
required to drive an IPM
motor are set.
The parameters settings
required to drive an IPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance. (Refer to
page 5-454.))
The parameters settings
required to drive an SPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance. (Refer to
page 5-454.))