Inverter rating
8.1.2

400 V class

Model FR-A840-
SLD
LD
Applicable motor
capacity [kW]
ND (initial setting)
HD
SLD
LD
Rated capacity
[kVA]
ND (initial setting)
HD
SLD
LD
Rated current
[A]
ND (initial setting)
HD
SLD
Overload
LD
current rating
ND (initial setting)
HD
Rated voltage
Brake transistor
Maximum brake
Regenerative
torque
braking
FR-ABR (when
the option is
used)
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
SLD
LD
Rated input
current [A]
ND (initial setting)
HD
SLD
Power supply
LD
capacity
ND (initial setting)
[kVA]
HD
Protective structure (IEC 60529)
Cooling system
Approx. mass [kg]
Tab. 8-2:
Specifications FR-A840-00023(0.4K) to 02600(90K)
For footnotes
8 - 2
00023
00038
00052
00083
00126
(0.4K)
(0.75K)
(1.5K)
(2.2K)
(3.7K)
0.75
1.5
2.2
3.7
5.5
0.75
1.5
2.2
3.7
5.5
0.4
0.75
1.5
2.2
3.7
0.4
0.75
1.5
2.2
0.2
1.8
2.9
4
6.3
10
1.6
2.7
3.7
5.8
8.8
1.1
1.9
3
4.6
6.9
0.6
1.1
1.9
3
4.6
2.3
3.8
5.2
8.3
12.6
2.1
3.5
4.8
7.6
11.5
1.5
2.5
4
6
9
0.8
1.5
2.5
4
6
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature 40 °C
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature 50 °C
150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature 50 °C
200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature 50 °C
100% torque/2%ED
100% torque/10%ED
3.2
5.4
7.8
10.9
16.4
3
4.9
7.3
10.1
15.1
2.3
3.7
6.2
8.3
12.3
1.4
2.3
3.7
6.2
8.3
2.5
4.1
5.9
8.3
12
2.3
3.7
5.5
7.7
12
1.7
2.8
4.7
6.3
9.4
1.1
1.7
2.8
4.7
6.3
Enclose type (IP20)
Self-cooling
2.8
2.8
2.8
3.3
3.3
to
refer to page 8-4.
00170
00250
00310
00380
00470
(5.5K)
(7.5K)
(11K)
(15K)
(18.5K)
7.5
11
15
18.5
22
7.5
11
15
18.5
22
5.5
7.5
11
15
18.5
3.7
5.5
7.5
11
15
13
19
24
29
36
12
18
22
27
33
9.1
13
18
24
29
6.9
9.1
13
18
24
17
25
31
38
47
16
23
29
35
43
12
17
23
31
38
9
12
17
23
31
Three-phase 380 to 500 V
Built-in
20% torque/continuous
100% torque/6%ED
Three-phase 380 to 500 V 50 Hz/60 Hz
323 to 550 V 50 Hz/60 Hz
±5%
22.5
31.7
40.3
48.2
58.4
22.3
31
38.2
44.9
53.9
17.4
22.5
31
40.3
48.2
12.3
17.4
22.5
31
40.3
17
24
31
37
44
17
24
29
34
41
13
17
24
31
37
9.4
13
17
24
31
Forced air cooling
6.7
6.7
8.3
8.3
15
Specifications
00620
00770
00930
01160
01800
(22K)
(30K)
(37K)
(45K)
(55K)
30
37
45
55
75/90
30
37
45
55
75
22
30
37
45
55
18.5
22
30
37
45
47
59
71
88
137
43
53
65
81
110
34
43
54
66
84
29
34
43
54
66
62
77
93
116
180
57
70
85
106
144
44
57
71
86
110
38
44
57
71
86
76.8
97.6
115
141
180
75.1
89.7
106
130
144
56.5
75.1
91
108
134
48.2
56.5
75.1
91
108
59
74
88
107
137
57
68
81
99
110
43
57
69
83
102
37
43
57
69
83
Open type (IP00)
15
23
41
41
43
02160
02600
(75K)
(90K)
110
132
90
110
75
90
55
75
165
198
137
165
110
137
84
110
216
260
180
216
144
180
110
144
FR-BU2(Option)
10% torque/
continuous
216
260
180
216
144
180
110
144
165
198
137
165
110
137
84
110
52
55