Basic operation
4.4

Frequently-used parameters (simple mode parameters)

Parameters that are frequently used for the FR-A800 series are grouped as simple mode parameters.
When Pr. 160 "User group read selection" = "9999", only the simple mode parameters are displayed.
This section explains about frequently-used parameters.
4.4.1
Simple mode parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used
as they are. Set the necessary parameters to meet the load and operational specifications. Parameter
setting, change and check can be performed from the operation panel (FR-DU08).
NOTE
Pr. 160 "User group read selection" can narrow down the displayed parameters to only the simple
mode parameters. (In the initial setting, all parameters are displayed.) Set Pr. 160 "User group read
selection" as required. (For the parameter change, refer to page 4-6.)
Pr. 160 setting
(initial value)
Tab. 4-8:
Pr.
Pr.
group
0
G000
1
H400
2
H401
3
G001
4
D301
5
D302
6
D303
7
F010
8
F011
Tab. 4-9:
FR-A800
Description
9999
Displays only the simple mode parameters.
0
Displays simple mode + extended parameters.
1
Displays parameters registered in the user group.
Setting of parameter 160
Name
Unit
Torque boost
0.1%
Maximum
0.01 Hz
frequency
Minimum
0.01 Hz
frequency
Base frequency
0.01 Hz 60 Hz 50 Hz 0–590 Hz
Multi-speed
setting (high
0.01 Hz 60 Hz 50 Hz 0–590 Hz
speed)
Multi-speed
setting (middle
0.01 Hz
speed)
Multi-speed
setting (low
0.01 Hz
speed)
Acceleration time
0.1 s
Deceleration time
0.1 s
Simple mode parameters (1)
Frequently-used parameters (simple mode parameters)
Initial value
Range
Application
FM
CA
6%
Set this parameter to obtain a higher
4%
starting torque under V/F control. Also set
0–30%
this when a loaded motor cannot be
3%
driven and the warning [OL] occurs, then
2%
the inverter trips with [OC1].
1%
120 Hz
Sets the upper limit for the output
0–120 Hz
frequency.
60 Hz
Sets the lower limit for the output
0Hz
0–120 Hz
frequency.
Set this parameter when the rated motor
frequency is 50 Hz.
Check the rating plate of the motor.
Pre-sets the speeds that will be switched
30 Hz
0–590 Hz
among by terminals.
10 Hz
0–590 Hz
5 s
0–3600 s
Sets the acceleration time.
15 s
5 s
0–3600 s
Sets the deceleration time.
15 s
Refer
to
page
5-652
5-310
5-654
4-16,
4-24,
5-189
5-233
4 - 11