Reset Method For The Protective Functions - Mitsubishi Electric FR-A820-00046 Instruction Manual

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Reset method for the protective functions

6.2
Reset method for the protective functions
Reset the inverter by performing any of the following operations. Note that the accumulated heat val-
ue of the electronic thermal relay function and the number of retries are cleared (erased) by resetting
the inverter.
The inverter recovers about 1 s after the reset is released.
● On the operation panel, press STOP/RESET key to reset the inverter.
(This may only be performed when a fault occurs. Refer to page 6-18 of the Instruction Manual
for faults.)
● Switch the power OFF once, then switch it ON again.
● Turn ON the reset signal (RES) for 0.1 s or more. (If the RES signal is kept ON, "Err" appears (flickers)
to indicate that the inverter is in a reset status.)
NOTE
OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an
inverter fault with the start signal ON restarts the motor suddenly.
6 - 2
ON
OFF
Inverter
RES
SD
Fig. 6-1:
Resetting the inverter by using the operation panel
Fig. 6-2:
Resetting the inverter by switching the power
supply off and on
Fig. 6-3:
Resetting the inverter by turning on the RES signal
Protective functions
I002451E
I001297E
I002452E

Hide quick links:

Advertisement

Table of Contents
loading