Setting The Frequency By Switches (Multi-Speed Setting) (Pr. 4 To Pr. 6) - Mitsubishi Electric FR-A820-00046 Instruction Manual

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Basic operation procedure (External operation)
4.6.2

Setting the frequency by switches (multi-speed setting) (Pr. 4 to Pr. 6)

NOTES
Switch ON the STF (STR) signal to give a start command.
Turn ON the RH, RM, or RL signal to give a frequency command. (Multi-speed setting)
Connection diagram
Switch
Fig. 4-9:
Example
Changing example: Operate at a high-speed (60 Hz).
Screen at power-ON
The monitor display appears.
Setting the frequency
Turn ON the high-speed switch (RH).
Start ➔ acceleration ➔ constant speed
Turn ON the start switch (STF or STR). The frequency value on the indication increases in Pr. 7 "Acceleration time", and
"
reverse rotation.
When RM is turned ON, 30 Hz is displayed. When RL is turned ON, 10 Hz is displayed.
Deceleration ➔ stop
Turn OFF the start switch (STF or STR).The frequency value on the indication decreases in Pr. 8 "Deceleration time", and
the motor stops rotating with "
speed switch (RH).
Tab. 4-16:
NOTES
When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter deceler-
ates to a stop.
The terminal RH is initially set to 60 Hz for the FM type inverter, and to 50 Hz for the CA type
inverter. The terminal RM is set to 30 Hz, and the RL is set to 10 Hz. (To change, set Pr. 4, Pr. 5, and
Pr. 6.)
In the initial setting, when two or more of multi-speed settings are simultaneously selected, prior-
ity is given to the set frequency of the lower signal.
For example, when RH and RM signals turn ON, RM signal (Pr. 5) has a higher priority.
Maximum of 15-speed operation can be performed.
4 - 24
Forward rotation start
Reverse rotation start
High speed
Middle speed
Low speed
Multi-speed setting in dependence on the terminals
" (60.00 Hz) appears. [FWD] indicator is lit during the forward rotation, and [REV] indicator is lit during the
Operate the inverter by using external signals
Inverter
STF
STR
RH
RM
RL
SD
Operation
" (0.00 Hz) displayed. [FWD] or [REV] indicator turns OFF. Turn OFF the high-
Basic operation
Speed 1 (High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
ON
RH
ON
RM
ON
RL
I002436E, I002444E