Fig. 5-290:
● For the standard model, remove the jumpers between terminals R/L1 and R1/L11 and terminals
S/L2 and S1/L21, and connect terminals R1/L11 and P/+ and terminals S1/L21 and N/–.
● If an undervoltage, power failure or input phase loss occurs when Pr. 261 "Power failure stop
selection" ≠ "0", the motor decelerates to a stop.
● The power failure time deceleration stop function operates as follows at an input phase loss.
Pr. 261
0
1, 2
21, 22
Tab. 5-251: Operation at input phase loss depending on Pr. 261 and Pr. 872
● For the separated converter type, remove the jumpers between terminals R/L1 and R1/L11 and
terminals S/L2 and S1/L21 of the converter unit, and connect terminals R1/L11 and P/+ and
terminals S1/L21 and N/–. Do not remove the jumpers of terminal R1/L11 and terminal S1/L21 of
the inverter. (In the initial status of the separated converter type, terminals P/+ and R1/L11 and
terminals N/- and S1/L21 are connected.)
● For the separated converter type, connect the terminal to which PWF signal of the converter unit
is assigned and the terminal to which X48 signal of the inverter is assigned. Also, set Pr. 261 of the
converter unit in accordance with the inverter setting. (Refer to the Instruction Manual of the
converter unit.)
Outline of operation of deceleration stop at a power failure
● If an undervoltage or power failure occurs, the output frequency is turned OFF only for the
frequency set to Pr. 262 "Subtracted frequency at deceleration start".
● The motor decelerates for the time set to Pr. 264 "Power-failure deceleration time 1". (The decel-
eration time setting is the time it takes for the motor to stop from Pr. 20 "Acceleration/deceleration
reference frequency".)
● Change the deceleration time (slope) to the stop using Pr. 265 "Power-failure deceleration time"
FR-A800
Power supply
Remove the jumper
Connection of the separated converter type inverter
Pr. 872
Operation when an input phase loss occurs
0
Continuous operation
1
Input phase loss (E.ILT)
0
Continuous operation
1
Deceleration stop
Deceleration stop
Keep the jumpers of terminal R1/L11 and
terminal S1/L21 connected.
Converter unit
R/L1
P/+
S/L2
N/-
T/L3
R1/L11
S1/L21
RDA
RSO
PWF
SE
(A) Application parameters
Inverter
P/+
U
N/-
V
M
W
R1/L11
S1/L21
MRS(X10)
RES
X48
SD
I002875E
5 - 581