Parameters
Types of
monitor
Load meter
Motor excitation
current
Position pulse
Cumulative
energization
time
Orientation
status
Actual operation
time
Motor load
factor
Cumulative
power
Position
command
(lower digits)
Position
command
(upper digits)
Current position
(lower digits)
Current position
(upper digits)
Droop pulse
(lower digits)
Droop pulse
(upper digits)
Torque
command
Tab. 5-126: Monitor description list (2)
FR-A800
Pr. 52,
Unit
Pr. 774 to Pr. 776,
Pr. 992
0.1%
17
0.01 A/
18
0.1 A
19
1 h
20
1
22
1 h
23
0.1%
24
0.01 kWh/
0.1 kWh
25
1
26
1
27
1
28
1
29
1
30
1
31
0.1%
32
(M) Monitor display and monitor output signal
RS-485
communica-
MODBUS
tion dedicat-
RTU real
Minus (-)
ed monitor
time
display
(hexadeci-
monitor
mal)
H11
40217
H12
40218
H13
40219
H14
40220
H16
40222
H17
40223
H18
40224
H19
40225
H1A
40226
H1B
40227
H1C
40228
H1D
40229
H1E
40230
H1F
40231
H20
40232
Description
Displays torque current as a
percentage, considering Pr. 56
setting value as 100% (motor
rated torque is considered as
100% during Sensorless vector
and vector control).
Displays the motor excitation
current
Displays the number of pulses
per motor rotation during
orientation control and position
control. (Displays the voltage
monitor when a vector control
compatible option is not
connected.)
Displays the cumulative
energization time since the
inverter shipment.
Check how many times the
monitor value exceeded 65535 h
with Pr. 563.
Displays values only when
orientation control is enabled.
(Displays the voltage monitor
when a vector control
compatible option is not
connected.)
(Refer to page page 5-503)
Displays the cumulative time
since the inverter began running.
The number of times the monitor
value exceeded 65535 h can be
checked with Pr. 564.
This can be cleared with Pr. 171.
(Refer to page 5-337)
Displays the output current
value as a percentage,
considering the inverter rated
current value as 100%.
Monitor value = output current
monitor value / inverter rated
current × 100 [%]
Displays the cumulative energy
based on the output power
monitor.
This can be cleared with Pr. 170.
(Refer to page 5-337.)
Displays the position command
(decimal) before the electronic
gear is set.
Displays the value of the position
feedback pulse after converting
it into the number of pulses
before the electronic gear is set.
Displays the droop pulse before
the electronic gear.
Displays the torque command
value obtained from the vector
control results.
5 - 329