Basic operation
4.6.4
Changing the frequency (60 Hz, initial value) at the maximum voltage input
(5 V, initial value)
Change the maximum frequency
Example
Changing example
With a 0 to 5 V DC input frequency setting potentiometer, change the frequency at 5 V from 60 Hz
(initial value) to 50 Hz.
Adjust the setting so that the inverter outputs 50 Hz when 5 V is input. Set "50 Hz" in Pr. 125.
Parameter selection
Turn
Press
Changing the maximum frequency
Turn
Press
Checking the mode/monitor
Press
Start
Turn ON the start switch (STF or STR), then turn the potentiometer (frequency setting potentiometer) clockwise slowly
to full. (Refer to steps
Tab. 4-18:
NOTES
To set the frequency at 0 V, use the calibration parameter C2.
Other adjustment methods for the frequency setting voltage gain are the following: adjustment
by applying a voltage directly across terminals 2 and 5, and adjustment using a specified point
without applying a voltage across terminals 2 and 5.
Parameters referred to
Pr. 125
C2 (Pr. 902)
C4 (Pr. 903)
FR-A800
until
(Pr. 125) appears.
to show the present set value. (60.00 Hz)
to change the set value to "
to enter the setting."
three times to change to the monitor / frequency monitor.
and
in section 4.6.3.) Operate at 50 Hz.
Change the frequency of the maximum analog value
60 Hz
(50 Hz)
Output frequency [Hz]
Bias
C2 (Pr. 902)
0
Frequency setting signal
0
0
C3 (Pr. 902)
Terminal 2 frequency setting gain frequency
Terminal 2 frequency setting bias frequency
Terminal 2 frequency setting gain
Basic operation procedure (External operation)
Operation
". (50.00 Hz)
" and "
" flicker alternately.
Initial value
Gain Pr. 125
100%
5 V
10 V
C4 (Pr. 903)
=>