Mitsubishi Electric FR-A820-00046 Instruction Manual page 497

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
Adjusting the stall prevention operation signal output and output timing (OL signal, Pr. 157)
● If the output current exceeds the stall prevention operation level and stall prevention is activated,
Overload warning (OL) signal will turn ON for 100 ms or more. The output signal turns OFF when
the output current falls to the stall prevention operation level or less.
● Pr. 157 "OL signal output timer" can set whether to output the OL signal immediately, or to output
it after a certain time period.
● This function also operates during regeneration avoidance operation
Tab. 5-121: Setting of parameter 157
Overload state
(OL operation)
OL output signal
NOTES
OL signal is assigned to the terminal OL in the initial status. The OL signal can be assigned to other
terminals by setting "3 (positive logic) or 103 (negative logic)" in any of Pr. 190 to Pr. 196 (output
terminal function selection).
If the stall prevention operation has lowered the output frequency to 0.5 Hz and kept the level for
3 s, the stall prevention stop (E.OLT) is activated to shut off the inverter output.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
FR-A800
Pr. 157 setting
0 (initial value)
0.1 to 25
9999
Pr. 157 Set time (s)
(H) Protective function parameter
Description
Output immediately.
Output after the set time (s).
Not output.
Fig. 5-140:
Output of the OL signal
(overvoltage stall).
I002515E
5 - 317