Parameters
Types of
monitor
Input terminal
status
Output terminal
status
Option input
terminal status
Option output
terminal status
Option input
terminal status 1
(for
communication)
Option input
terminal status 2
(for communica-
tion)
Option output
terminal status 1
(for communica-
tion)
Motor thermal
load factor
Inverter thermal
load factor
PTC thermistor
resistance
PID measured
value 2
Cumulative
pulse
Cumulative
pulse overflow
times
Cumulative
pulse (control
terminal option)
Tab. 5-126: Monitor description list (4)
FR-A800
Pr. 52,
Unit
Pr. 774 to Pr. 776,
Pr. 992
—
55
—
—
56
—
—
57
—
—
—
—
—
—
—
0.1%
61
0.1%
62
0.01 kΩ
64
0.1%
67
—
71
—
72
—
73
(M) Monitor display and monitor output signal
RS-485
communica-
MODBUS
tion dedicat-
RTU real
Minus (-)
ed monitor
time
display
(hexadeci-
monitor
mal)
H0F
40215
H10
40216
—
—
—
—
H3A
40258
H3B
40259
H3C
40260
H3D
40261
H3E
40262
H40
40264
H43
40267
H47
40271
H48
40272
H49
40273
Description
Displays input terminal ON/OFF
state of the inverter. (Refer to
page 5-336 for DU display.)
Displays output terminal ON/OFF
state of the inverter. (Refer to
page 5-336 for DU display.)
Displays input terminal ON/OFF
state of the digital input option
(FR-A8AX) on the DU.
(Refer to page 5-336 for details.)
Displays output terminal ON/OFF
state of the digital output option
(FR-A8AY) and the relay output
option (FR-A8AR) on the DU.
(Refer to page 5-336 for details.)
Input terminal X0 to X15 ON/OFF
state of the digital input option
(FR-A8AX) can be monitored via
RS-485 communication and the
communication option.
Input terminal DY ON/OFF state
of the digital input option
(FR-A8AX) can be monitored via
RS-485 communication and the
communication option.
Output terminal ON/OFF state of
the digital output option
(FR-A8AY) and relay output
option (FR-A8AR) can be
monitored via RS-485
communication and the
communication option.
Displays the accumulated heat
value of the motor thermal O/L
relay.
The motor overload trip (E.THM)
occurs at 100%.
Displays the accumulated heat
value of the inverter thermal O/L
relay.
The inverter overload trip (E.THT)
occurs at 100%.
Displays the PTC thermistor
resistance when Pr. 561 "PTC
thermistor protection level" ≠
9999 (voltage monitor when
Pr. 561 = 9999).
Displays the PID control
measured value even if PID
control operating conditions are
not satisfied while the PID
control is enabled (Pr.128 ≠ "0").
(Refer to page 5-537)
The cumulative number of
pulses is displayed (monitor
range: –32767 to 32767)
(for FR-A8AP/FR-A8APR).
The number of the cumulative
pulse carrying-over times is
displayed (for FRA8AP/
FR-A8APR).
The cumulative number of
pulses is displayed (monitor
range: –32767 to 32767)
(for FR-A8TP).
5 - 331