Mitsubishi Electric FR-A820-00046 Instruction Manual page 196

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameter List
Pr.
Pr.
Name
group
503
E710
Maintenance timer 1
Maintenance timer 1 warning output
504
E711
set time
505
M001
Speed setting reference
516
F400
S-pattern time at a start of acceleration
S-pattern time at a completion of
517
F401
acceleration
518
F402
S-pattern time at a start of deceleration
S-pattern time at a completion of
519
F403
deceleration
522
G105
Output stop frequency
MODBUS RTU communication check
539
N002
time interval
547
N040
USB communication station number
USB communication check time
548
N041
interval
549
N000
Protocol selection
NET mode operation command source
550
D012
selection
PU mode operation command source
551
D013
selection
552
H429
Frequency jump range
553
A603
PID deviation limit
554
A604
PID signal operation selection
555
E720
Current average time
556
E721
Data output mask time
Current average value monitor signal
557
E722
output reference current
560
A712
Second frequency search gain
561
H020
PTC thermistor protection level
563
M021
Energization time carrying-over times
564
M031
Operating time carrying-over times
569
G942
Second motor speed control gain
570
E301
Multiple rating setting
571
F103
Holding time at a start
A680
573
4 mA input check selection
T052
574
C211
Second motor online auto tuning
Tab. 5-2:
Parameter overview (by number) (15)
5 - 16
Minimum
Setting range
setting
increments
0 (1 to 9998)
1
0 to 9998, 9999
1
1 to 590 Hz
0.01 Hz
0.1 to 2.5 s
0.1 s
0.1 to 2.5 s
0.1 s
0.1 to 2.5 s
0.1 s
0.1 to 2.5 s
0.1 s
0 to 590 Hz, 9999
0.01 Hz
0 to 999.8 s, 9999
0.1 s
0 to 31
1
0 to 999.8 s, 9999
0.1 s
0, 1
1
0, 1, 9999
1
1 to 3, 9999
1
0 to 30 Hz, 9999
0.01 Hz
0.0 to 100%, 9999
0.1%
0 to 3, 10 to 13
1
0.1 to 1 s
0.1 s
0 to 20 s
0.1 s
0 to 500 A
0.01 A
0 to 3600 A
0.1 A
0 to 32767, 9999
1
0.5 to 30 kΩ, 9999
0.01 kΩ
(0 to 65535)
1
(0 to 65535)
1
0 to 200%, 9999
0.1%
0 to 3
1
1,2
0 to 10 s, 9999
0.1 s
1 to 4, 9999
1
0 to 2
1
Parameters
Initial value
Refer
to page
FM
CA
0
5-227
9999
5-227
60 Hz
50 Hz
5-324
0.1 s
5-240
0.1 s
5-240
0.1 s
5-240
0.1 s
5-240
9999
5-671
9999
5-630
0
5-648
9999
5-648
0
5-606
9999
5-274
9999
5-274
9999
5-312
9999
5-524
0
5-524
1 s
5-229
0 s
5-229
Rated inverter
5-229
current
9999
5-562
9999
5-292
0
5-327
0
5-327
9999
5-67
2
5-201
9999
5-251
9999
5-399
0
5-465