Download Print this page

Remote Output Function - Mitsubishi Electric FR-E800 Instruction Manual

Advertisement

12.10

Remote output function

The signal can be turned ON or OFF via the output terminal on the inverter as if the terminal is the remote output terminal for
a programmable controller.
Pr.
Name
495
Remote output selection 0
M500
496
Remote output data 1
M501
497
Remote output data 2
M502
 Remote output setting (REM signal, Pr.496, Pr.497)
• The signal assigned to each of the output terminal can be turned ON or OFF according to the settings of Pr.496 and Pr.497.
The signal assigned to each of the remote output terminal can be turned ON or OFF through communication.
• For the Remote output (REM) signal, set "96" (positive logic) or "196" (negative logic) in any parameter from Pr.190 to
Pr.192, and Pr.197 (Output terminal function selection) to assign the function to an output terminal.
• Refer to the following figures to check correspondences between the bit and the actual terminal. When "1" is set in the bit
corresponding to the terminal to which the REM signal assigned by setting a number in Pr.496 and Pr.497 each, the signal
turns ON (or OFF in negative logic setting). Also, setting "0" allows the signal to turn OFF (or ON in negative logic setting).
• For example, when Pr.190 RUN terminal function selection = "96" (positive logic) and "1" (H01) is set in Pr.496, the REM
signal assigned to terminal RUN turns ON.
Pr.496
b11
Pr.497
b11
*1
Any value
*2
Y0 to Y6 are available by installing the output-extending option (FR-A8AY) or via communication.
*3
Y1 and Y2 are available by installing the input/output-extending option (FR-E8AXY) or via communication.
*4
RA1 to RA3 are available by installing the relay output option (FR-A8AR) or via communication.
*5
For models without physical terminals, signals can be output only via communication.
 Remote output data retention (REM signal, Pr.495)
• When the inverter power is reset (or a power failure occurs) while Pr.495 = "0 (initial value) or 10", the REM signal setting
is cleared. (The ON/OFF state of the signal assigned to each terminal is determined by the settings in Pr.190 to Pr.192,
and Pr.197.) The settings in Pr.496 and Pr.497 are reset to "0".
• When Pr.495 = "1 or 11", the remote output data is stored in EEPROM before the inverter power is turned OFF. This means
that the signal output setting after power restoration is the same as that before the power was turned OFF. However, when
Pr.495 = "1", the data during an inverter reset (terminal reset or reset request via communication) is not saved.
388
12. (M) Item and Output Signal for Monitoring
12.10 Remote output function
Setting
Initial value
range
Remote output data is cleared when
0
the inverter power is turned OFF.
Remote output data is retained even
1
after the inverter power is turned OFF.
Remote output data is cleared when
10
the inverter power is turned OFF.
Remote output data is retained even
11
after the inverter power is turned OFF.
Set a decimal number to enter a binary number in every bit
0
0 to 4095
corresponding to each of the output terminals of the inverter or
communication.
Set a decimal number to enter a binary number in every bit
0
0 to 4095
corresponding to each of the output terminals of the option FR-A8AY,
FR-E8AXY, or FR-A8AR, or communication.
b0
b0
Description
Remote output data is cleared
during an inverter reset.
Remote output data is retained
during an inverter reset.

Advertisement

loading