Parameters
Regenerative status output signal (Y32)
Fig. 5-168:
● When the motor is in the regenerative status (motor is in the dynamic braking status) under vector
control, the Regenerative status output (Y32) signal turns ON. Once it turns ON, the signal is
retained for at least 100 ms.
● The signal turns OFF during a stop or pre-excitation.
● To use the Y32 signal, set "32 (positive logic) or 132 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
NOTES
Always OFF under V/F control, Advanced magnetic flux vector control, Real sensorless vector con-
trol, and PM sensorless vector control.
Fault output signals (ALM, ALM2)
Fig. 5-169:
● The Fault (ALM, ALM2) signals are output when the inverter protective function is activated.
● The ALM2 signal stays ON during the reset period after the fault occurs.
● To use the ALM2 signal, set "94 (positive logic) or 194 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
● The ALM signal is assigned to the A1B1C1 contacts in the initial status.
NOTE
For the inverter fault details, refer to page 6-9.
FR-A800
Driving
+
Regeneration
Y32
Forward and reverse rotation of the motor
Inverter alarm occurrence (trip)
ON
ALM
ON
ALM2
RES
Reset ON
Fault signals
(M) Monitor display and monitor output signal
Less than 100 ms
ON
OFF
ON
Signal is retained for 100 ms.
OFF
OFF
ON
OFF
Reset processing
(about 1s)
Time
I002625E
Time
I001153E
5 - 371