Mitsubishi Electric FR-A820-00046 Instruction Manual page 710

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(A) Application parameters
Connection diagram
Sink logic
Pr. 128 = 20
Pr. 183 = 14
Pr. 191 = 47
Pr. 192 = 16
Pr. 193 = 14
Pr. 194 = 15
Fig. 5-262:
Prepare a power supply matched to the power supply specification of the detector.
The output signal terminal to be used differs according to the Pr. 190 to Pr. 196 (output terminal
function selection) setting.
The input signal terminal to be used differs according to the Pr. 178 to Pr. 189 (input terminal
function selection) setting.
The AU signal need not be input.
5 - 530
MCCB
Power supply
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
AC1φ
200/220 V 50/60 Hz
Connection diagram in sink logic
Inverter
Motor
R/L1
U
S/L2
V
T/L3
W
STF
STR
RT(X14)
During PID action
(PID)SU
SD
Upper limit
(FUP)FU
Lower limit
(FDN)OL
10
Forward rotation
2
(RL)IPF
output
Reverse rotation
5
output
1
Output signal common
SE
4
(Measured value) 4 to 20 mA
24 V
0
Power
supply
Parameters
Pump
M
P
2-wire type
3-wire
type
Detector
-
-
+
+
+
(OUT)
(COM)
(24 V)
I002692E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents