Parameters
5.7.10

Multiple rating setting

Four rating types of different rated current and permissible load can be selected. The optimal inverter
rating can be chosen in accordance with the application, enabling equipment size to be reduced.
Pr.
570
E301
Not compatible with the IP55 compatible model.
Changing the parameter initial values and setting ranges
● When inverter reset and all parameter clear are performed after setting Pr. 570, the parameter
initial values are changed according to each rating, as shown below.
Pr.
Name
0
Torque boost
7
Acceleration time
8
Deceleration time
9
Electronic thermal O/L relay
12
DC injection brake operation voltage
22
Stall prevention operation level
Second stall prevention operation
48
level
56
Current monitoring reference
114
Third stall prevention operation level
148
Stall prevention level at 0 V input
149
Stall prevention level at 10 V input
150
Output current detection level
Stall prevention operation level for
165
restart
Current average value monitor signal
557
output reference current
874
OLT level setting
Energy saving monitor reference
893
(motor capacity)
Tab. 5-71:
FR-A800
Name
Multiple rating setting
Influence of Pr. 570 on other parameters
(E) Environment setting parameters
Setting
Description (overload current rating,
Initial value
range
surrounding air temperature)
SLD rating
110% 60 s, 120% 3 s (inverse-time
0
characteristics)
Surrounding air temperature 40 °C
LD rating
120% 60 s, 150% 3 s (inverse-time
1
characteristics)
Surrounding air temperature 50 °C
2
ND rating
150% 60 s, 200% 3 s (inverse-time
2
characteristics)
Surrounding air temperature 50 °C
HD rating
200% 60 s, 250% 3 s (inverse-time
3
characteristics)
Surrounding air temperature 50 °C
Pr. 570 setting
0
1
SLD rated
LD rated
current
current
110%
120%
110%
120%
SLD rated
LD rated
current
current
110%
120%
110%
120%
120%
150%
110%
120%
110%
120%
SLD rated
LD rated
current
current
110%
120%
SLD rated
LD rated motor
motor
capacity
capacity
2 (Initial
3
value)
ND rated
HD rated
current
current
150%
200%
150%
200%
ND rated
HD rated
current
current
150%
200%
150%
200%
200%
250%
150%
200%
150%
200%
ND rated
HD rated
current
current
150%
200%
ND rated
HD rated
motor
motor
capacity
capacity
Refer
to
5-652
5-233
5-233
5-292
5-663
5-84,
5-314
5-314
5-341
5-314
5-314
5-314
5-377
5-562
5-229
5-84
5-189
5 - 201

Hide quick links: