Basic operation
NOTES
Pr. 184 "AU terminal function selection" must be set to "4" (AU signal) (initial value).
To change the frequency (60 Hz) at the maximum current input (initial value 20 mA), adjust Pr. 126
"Terminal 4 frequency setting gain frequency".
To change the frequency (0 Hz) at the minimum current input (initial value 4 mA), adjust the cali-
bration parameter C5 "Terminal 4 frequency setting bias frequency".
Parameters referred to
Pr. 7
Pr. 8
Pr. 79
Pr. 126
Pr. 184
C5 (Pr. 904)
FR-A800
Acceleration time
Deceleration time
Operation mode selection
Terminal 4 frequency setting gain frequency
AU terminal function selection
Terminal 4 frequency setting bias frequency
Basic operation procedure (PU operation)
=>
page 5-233
=>
page 5-233
=>
page 5-263
=>
page 5-401
=>
page 5-422
=>
page 5-401
4 - 21