Mitsubishi Electric FR-A820-00046 Instruction Manual page 653

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
MCCB
Fig. 5-221:
Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr. 190 to Pr. 196 (output terminal function selection).
Output terminal capacity
Open collector output of inverter (RUN, SU, IPF, OL, FU)
Inverter relay output (A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option (FR-A8AR)
When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use the relay output option (FR-A8AR) and use contact
outputs.
The applied terminals differ by the settings of Pr. 180 to Pr. 189 (input terminal function selection).
To use the signal, assign the function to the output terminal Pr. 190 to Pr. 195 (output terminal
function selection) of the converter unit. Always set the negative logic for the ALM signal.
NOTES
Use the electronic bypass function in External operation mode. In addition, the wiring terminals
R1/L11 and S1/L21 must be connected to a separate power source that does go through MC1. Be
sure to connect using a separate power supply.
Be sure to provide a mechanical interlock for MC2 and MC3.
FR-A800
Converter unit
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
RDA
External thermal
OH
Y214
Reset
RES
RSO
SD
Electronic bypass sequence connection diagram (Separated converter type)
Separated converter type
P/+
N/-
Inverter start
(forward rotation)
Inverter/bypass
operation interlock
SE
ALM
Frequency
setting signal
(A) Application parameters
MC2
Inverter
MC3
P/+
U
V
N/-
W
STF
CS
MRS
SD
MC1
X10
MC3
X95
MC2
X96
RES
MC2
10
MC3
2
5
SE
R1/L11
S1/L21
Output terminal permissible load
24 V DC 0.1 A
230 V AC 0.3 A
30 V DC 0.3 A
External
thermal relay
IM
MC1
MC2
24 V DC
MC3
I002848E_F
5 - 473