(A) Application parameters
● Separated converter types detect the instantaneous power failure on the converter unit side.
Perform wiring so that the IPF signal transmitted from the converter unit is input to the terminal
to which the X11 signal is assigned.
On the converter unit side, enable the restart operation. (For setting the converter unit, refer to
the Instruction Manual of the converter unit.)
● For the terminal to be used for the X10 and X11 signal, set "10" (X10), "11" (X11) in Pr. 178 to Pr.
189 and assign the function. (For separated converter types, the X10 signal is assigned to the
terminal MRS in the initial setting.)
● For the X10 signal of separated converter types, NC contact input specification is selected in the
initial setting. Set Pr. 599 = "0" to change the input specification to NO contact.
NOTES
The CS signal is assigned to terminal CS in the initial setting. By setting "6" to any of Pr. 178 to
Pr. 189 (input terminal function selection), the CS signal can be assigned to other terminals.
Changing the terminal assignment using Pr. 178 to Pr. 189 may affect other functions. Set parame-
ters after confirming the function of each terminal.
If the CS signal is not assigned to any input terminal, solely setting Pr. 57 will enable the restart
operation at all times.
5 - 564
Converter unit
Inverter
RDA
X10
IPF
X11
CS
SE
SD
Separated converter type
Fig. 5-282: Connecting the signals X10, X11, CS
Parameters
I002850E