Mitsubishi Electric FR-A820-00046 Instruction Manual page 239

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
The setting values of 100 and above are used when the fast-response operation is selected.
Advanced magnetic flux vector control if a vector control compatible option is not installed.
The operation for the setting of "10 or 110" is performed when "13, 14, 113, or 114" is set.
The operation for the setting of "20 or 110" is performed when a value other than "9, 13, 14, 109,
113, or 114" is set.
The operation for the setting of "20 or 110" is performed when a value other than "13, 14, 113, 114,
or 9999" is set.
The operation for the setting of "20 or 110" is performed when a value other than "9 or 109" is set.
The operation for the setting of "20 or 110" is performed when a value other than "9999" is set.
V/F control when Pr. 80 or Pr. 81 is "9999", regardless of the Pr. 800 setting. When Pr. 71 is set to the
IPM motor MM-CF, PM sensorless vector control is enabled even if Pr. 80 ≠ "9999" or Pr. 81 = "9999".
Setting Pr. 788 (Pr. 747) = "0" (low-speed range torque characteristic disabled) selects speed control.
Selecting the fast-response operation (Pr. 800 (Pr. 451) = "100 to 106, 109 to 114")
Setting Pr. 800 = "any of 100 to 106 or 109 to 114" selects the fast-response operation. The fast-re-
sponse operation is available during vector control, Real sensorless vector control, and PM sensorless
vector control.
Control method
Vector control
Real sensorless vector control
PM sensorless vector control
Tab. 5-18:
When driving a 3.7 kW no-load motor.
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
NOTES
During fast-response operation, the carrier frequency is always 4 kHz. (Refer to page 237.)
E.THT is more likely to occur when fast-response operation is set at the SLD or LD rating.
FR-A800
Pr. 800 (Pr. 451) = "100 to 106, 109 to
Selecting the fast-response operation
Speed response
Fast-response operation
114"
130 Hz at maximum
50 Hz at maximum
50 Hz at maximum
Control method
Normal-response operation
Pr. 800 (Pr. 451) = "0 to 6, 9 to 14"
50 Hz at maximum
20 Hz at maximum
10 Hz at maximum
30 Hz at maximum
5 - 59