Parameters
Emergency stop function (Pr. 1103)
● When the emergency stop (X92) signal is ON, the deceleration stop is performed according to the
settings in the Pr. 1103 "Deceleration time at emergency stop" and Pr. 815 "Torque limit level 2".
● To input the X92 signal, set "92" in any of Pr. 178 to Pr. 189 (input terminal function selection) to
assign the function to a terminal.
● The X92 signal is a normally closed input (NC contact input).
● [PS] is displayed on the operation panel during activation of the emergency stop function.
Fig. 5-88:
NOTE
The X92 signals can be assigned to an input terminal by setting Pr. 178 to Pr. 189 (input terminal
function selection). Changing the terminal assignment may affect other functions. Set parameters
after confirming the function of each terminal.
Parameters referred to
Pr. 3
Pr. 10
Pr. 29
Pr. 125, Pr. 126
Pr. 178 to Pr. 182
Pr. 264
Pr. 265
FR-A800
(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Output frequency
[Hz]
Start signal
X92
Setting the acceleration/deceleration time in the low-speed range
Base frequency
DC injection brake operation frequency
Acceleration/deceleration pattern selection
(frequency setting gain frequency)
(input terminal function selection)
Power-failure deceleration time 1
Power-failure deceleration time 2
Deceleration by an
emergency stop
Normal
acceleration
Time
ON
OFF
ON
ON
OFF
ON
I002831E
=>