Fault Definition - Mitsubishi Electric FR-A820-00046 Instruction Manual

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(H) Protective function parameter
5.10.2

Fault definition

Fault output can be done after deceleration stop when motor thermal protection is activated.
Pr.
875
H030
Output shutoff at activation of any protective function (Pr. 875 = "0", initial value)
At activation of a protective function, output is shut off, and the alarm output 2 signal (ER) and the
fault signal (ALM) are output.
Deceleration stop at motor thermal protection activation (Pr. 875 = "1")
● At activation of the external thermal relay (E.OHT), motor load (electronic thermal O/L relay)
(E.THM) and PTC thermistor (E.PTC) protective functions, the alarm output 2 (ER) signal is dis-
played, and the motor decelerates to stop. After it stops, a fault signal (ALM) is output.
● When the ER signal comes ON, reduce the load or take other measures to allow the inverter to
decelerate.
● During fault occurrence aside from the E.OHT, E.THM and E.PTC, the output is immediately shut
off, and the fault signal (ALM) is output.
● To use the ER signal, set "97 (positive logic)" or "197 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
When Pr. 875 = "1"
frequency
Fault output
(ALM, ALM2)
Alarm output 2
NOTES
Regardless of the Pr. 875 setting, when the protective function is operating during position con-
trol, output is immediately shut off. (No deceleration stop)
For systems with a large load-side torque that prevents deceleration, setting value "0" is recom-
mended.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
5 - 302
Name
Fault definition
Output
ON
(ER)
E.OHT
occurrence
Initial
Setting
Description
value
range
0
Normal operation
0
Decelerates to stop at activation of motor thermal
1
protection.
Fig. 5-134:
Alarm output (Pr. 875 = 1)
Time
ON
E.OHT
display
Parameters
I002588E