(E) Environment setting parameters
Automatic parameter setting (Pr. 999)
Select which parameters to automatically set from the table below, and set them in Pr. 999. Multiple
parameter settings are changed automatically. Refer to page 5-214 for the list of parameters that are
changed automatically.
Pr. 999
Setting
1
2
10
11
12
13
20
21
Tab. 5-79:
NOTE
If the automatic setting is performed with Pr. 999 or the automatic parameter setting mode, the
settings including the changed parameter settings (changed from the initial setting) will be auto-
matically changed. Before performing the automatic setting, confirm that changing the parame-
ters will not cause any problem.
5 - 212
Description
Sets the standard monitor indicator setting of PID control.
Automatically sets the monitor indicator for PID control.
Automatically sets the communication parameters for the
GOT connection with a PU connector ("Controller Type" in
GOT: FREQROL 500/700/800, SENSORLESS SERVO)
Automatically sets the communication parameters for the
GOT connection with RS-485 terminals ("Controller Type"
in GOT: FREQROL 500/700/800, SENSORLESS SERVO)
Automatically sets the communication parameters for the
GOT connection with a PU connector ("Controller Type" in
GOT: FREQROL 800(Automatic Negotiation))
Automatically sets the communication parameters for the
GOT connection with RS-485 terminals ("Controller Type"
in GOT: FREQROL 800(Automatic Negotiation))
50 Hz rated
Sets the related parameters of the
frequency
rated frequency according to the
60 Hz rated
power supply frequency
frequency
Automatic parameter setting
Operation in the automatic parameter setting
mode
(AUTO) →
(AUTO) →
(AUTO) →
(AUTO) →
(AUTO) →
Parameters
(PID) → Write "1"
(PID) → Write "2"
(GOT) → Write "1"
(GOT) → Write "2"
(F50) → Write "1"