Parameter
6.10.8

Remote output function (REM, Pr. 495 to Pr. 497)

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of the
programmable logic controller.
Pr.
Name
Initial Value
No.
495
Remote output selection
496
Remote output data 1
497
Remote output data 2
The above parameters can be set when Pr. 160 "User group read selection" = 0.
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending onthe Pr. 496 or Pr. 497 setting. The remote out-
put selection can be controlled on/off by computer link communication from the PU connector or by
communication from the communication option.
Set "96" (positive logic) or "196" (negative logic) to any of Pr. 190 to Pr. 192 "Output terminal function
selection", and assign the remote output (REM) signal to the terminal used for remote output.
FR-E700SC EC
Setting
Description
Range
Remote output data clear at
0
powering off
Remote output data retention
1
at powering off
0
Remote output data clear at
10
powering off
Remote output data retention
11
at powering off
0
0–4095
Refer to Fig. 6-65
0
0–4095
Function assignment of external terminals
Parameters referred to
190–192 Output terminal
Remote output data clear
at inverter reset
Remote output data
retention at inverter
reset
Refer to
Section
6.10.5
function selection
6 - 133