(G) Control parameters
Setting multiple droop control types (Pr. 679 to Pr. 683)
When the second droop control is set, two droop control types can be switched. Turning ON the se-
cond function selection (RT) signal enables the second droop control.
NOTES
The RT signal is a second function selection signal. The RT signal also enables other second func-
tions.
The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr.178 to Pr.189
(input terminal function selection) to assign the RT signal to another terminal.
Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 1
Pr. 178 to Pr. 189
5 - 698
Maximum frequency
(input terminal function selection)
Parameters
=>
page 5-310
=>
page 5-422