Heatsink protrusion attachment procedure

When encasing the inverter to an enclosure, the heat generated in the enclosure can be greatly re-
duced by protruding the heatsink of the inverter.
When installing the inverter in a compact enclosure, etc., this installation method is recommended.
When using a heatsink protrusion attachment (FR-A8CN)
For the FR-A820-00105(1.5K) to 04750(90K) and the FR-A840-00023(0.4K) to 03610(132K), a heatsink
can be protruded outside the enclosure using a heatsink protrusion attachment (FR-A8CN). (For the
FR-A840-04320(160K) or higher, attachment is not necessary when the heatsink is to be protruded.)
For a panel cut dimension drawing and an installation procedure of the heatsink protrusion attach-
ment (FR-A8CN) to the inverter, refer to a manual of FR-A8CN.
Protrusion of heatsink of the FR-A840-04320(160K) or higher
● Panel cutting
Cut the panel of the enclosure according to the inverter capacity.
Tab. 2-6:
FR-A800
FR-A840-04320(160K),
FR-A840-04810(185K)
6-M10 screw
484
200
200
Hole
Dimensions of the cut-out for the heatsink protrusion
Installation of the inverter and enclosure design
Unit: mm
I002800E
FR-A840-05470(220K)
FR-A840-06100(250K)
FR-A840-06830(280K)
6-M10 screw
662
300
300
Hole
Unit: mm
I002801E
2 - 19