5.7.7

Resetting USB host errors

When a USB device is connected to the USB connector (connector A), the USB host error can be canceled without
performing an inverter reset.
Pr.
Name
1049
USB host reset
E110
• Parameter copy and the trace function can be used when a USB device (such as a USB memory) is connected to the USB
connector (connector A). (Refer to
• When a device such as a USB charger is connected to the USB connector and an excessive current (500 mA or higher)
flows, USB host error (UF warning) is displayed on the operation panel.
• If a UF warning occurs, disconnect the USB device and set Pr.1049="1" to cancel the USB error. (The UF warning can also
be canceled by resetting the inverter power or resetting with the RES signal.)
5.7.8

Multiple rating setting

Four rating types of different rated current and permissible load can be selected. The optimal inverter rating can be
chosen in accordance with the application, enabling equipment size to be reduced.
Pr.
Name
570
Multiple rating setting
E301
Overload current rating and surrounding air temperature
• The overload current rating of the inverter can be changed by the Pr.570 setting.
Pr.570
Rating
setting
0
SLD
110% 60 s, 120% 3 s (inverse-time characteristics)
1
LD
120% 60 s, 150% 3 s (inverse-time characteristics)
2
ND
150% 60 s, 200% 3 s (inverse-time characteristics)
200% 60 s, 250% 3 s, 280% 0.5 s (inverse-time
3
HD
characteristics)

30°C for the FR-A860-00090 or lower.
Changing the parameter initial values and setting ranges
• When inverter reset and all parameter clear are performed after setting Pr.570, the parameter initial values are changed
according to each rating, as shown below.
Pr.
Name
0
Torque boost
7
Acceleration time
8
Deceleration time
9
Electronic thermal O/L relay
22
Stall prevention operation level
48
Second stall prevention operation level
56
Current monitoring reference
114
Third stall prevention operation level
148
Stall prevention level at 0 V input
149
Stall prevention level at 10 V input
Initial value
0
page
58.)
Initial value
2
Overload current rating
0



SLD rated
current

110%
110%
SLD rated
current

110%
110%
120%
(E) Environment setting parameters
Setting range
0
Read only
1
Resets the USB host.
Setting
range
0
SLD rating
1
LD rating
2
ND rating
3
HD rating
Surrounding air temperature
FR-A860-01080 or lower
40°C

40°C
40°C
40°C
Pr.570 setting
2
1
(Initial value)






LD rated
ND rated
current
current


120%
150%
120%
150%
LD rated
ND rated
current
current


120%
150%
120%
150%
150%
200%
Description
Description
FR-A860-01440 or higher
40°C
50°C
50°C
40°C
Refer
to page
3
589

269

269

HD rated
317
current

200%
154,
332
200%
332
HD rated
357
current

200%
332
200%
332
250%
332
249
PARAMETERS