Hitachi WJ200-001S Instruction Manual page 79

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

230
2. Select the digital operator for RUN Command –
To RUN command causes the inverter to accelerate
the motor to the selected speed. The Run command
can arrive from various sources, including the
control terminals, the Run key on the keypad or the
network. In the figure to the right, notice the Run
Key Enable LED, just above the Run key. If the LED
is ON, the Run key is already selected as the source,
and you may skip this step. Note that the default
setting depends on the country.
If the Potentiometer Enable LED is OFF, follow these steps below (the table resumes
action from the end of the previous table).
(Starting point)
Press the
Press the SET key
Press the
Press the SET key to store
NOTE: After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time – complete the parameter setup first.
Action
key
key to select
/
Run Key Enable LED

RUN
ESC
Display
Func./Parameter

Speed command source setting

Run command source setting
Control terminal
Digital operator


ModBus network input
etc.

 Digital operator (selected)


Stores parameter, returns to ""
RUN
PWR
Hz
ALM
A
PRG
STOP/
1
RESET
2
SET

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents