Option
Terminal
Function Name
Code
Symbol
PID
PID Disable
PIDC
PID Reset
Remote Control UP
UP
Function (motorized
speed pot.)
Remote Control Down
DWN
Function (motorized
speed pot.)
Remote Control Data
UDC
Clearing
OPE
Operator Control
Multi-speed Select,
SF1
Bit operation Bit 1
Multi-speed Select,
SF2
Bit operation Bit 2
Multi-speed Select,
SF3
Bit operation Bit 3
Multi-speed Select,
SF4
Bit operation Bit 4
Multi-speed Select,
SF5
Bit operation Bit 5
Multi-speed Select,
SF6
Bit operation Bit 6
Multi-speed Select,
SF7
Bit operation Bit 7
Overload Restriction
OLR
Source Changeover
TL
Torque Limit Selection
TRQ1
Torque limit switch 1
TRQ2
Torque limit switch 2
Option
Terminal
Function Name
Code
Symbol
BOK
Brake confirmation
LAC
LAD cancellation
PCLR
Pulse counter clear
ADD
ADD frequency enable
Input Function Summary Table
Selects the direction of motor rotation: OFF = REV. While
OFF
the motor is rotating, a change of F/R will start a
deceleration, followed by a change in direction
Temporarily disables PID loop control. Inverter output turns
ON
OFF as long as PID Enable is active (=)
Has no effect on PID loop operation, which operates
OFF
normally if PID Enable is active (=)
Resets the PID loop controller. The main consequence is that
ON
the integrator sum is forced to zero
OFF
No effect on PID controller
Accelerates (increases output frequency) motor from current
ON
frequency
OFF
Output to motor operates normally
Decelerates (decreases output frequency) motor from current
ON
frequency
OFF
Output to motor operates normally
Clears the UP/DWN frequency memory by forcing it to equal
ON
the set frequency parameter F001. Setting must be
set= to enable this function to work
OFF
UP/DWN frequency memory is not changed
Forces the source of the output frequency setting and
ON
the source of the Run command to be from the digital
operator
Source of output frequency set by and source of Run
OFF
command set by is used
ON
Bit encoded speed select, Bit 1, logical 1
OFF
Bit encoded speed select, Bit 1, logical 0
ON
Bit encoded speed select, Bit 2, logical 1
OFF
Bit encoded speed select, Bit 2, logical 0
ON
Bit encoded speed select, Bit 3, logical 1
OFF
Bit encoded speed select, Bit 3, logical 0
ON
Bit encoded speed select, Bit 4, logical 1
OFF
Bit encoded speed select, Bit 4, logical 0
ON
Bit encoded speed select, Bit 5, logical 1
OFF
Bit encoded speed select, Bit 5, logical 0
ON
Bit encoded speed select, Bit 6, logical 1
OFF
Bit encoded speed select, Bit 6, logical 0
ON
Bit encoded speed select, Bit 7, logical 1
OFF
Bit encoded speed select, Bit 7, logical 0
ON
Perform overload restriction
OFF
Normal operation
ON
Setting of is enabled
OFF
Max. torque is limited with 200%
ON
Torque limit related parameters of Powering/regen, and
OFF
FW/RV modes are selected by the combinations of these
ON
inputs.
OFF
Input Function Summary Table
ON
Brake wait time () is valid
OFF
Brake wait time () is not valid
Set ramp times are ignored. Inverter output immediately
ON
follows the freq. command.
OFF
Accel. and/or decel. is according to the set ramp time
ON
Clear the position deviation data
OFF
Maintain the position deviation data
ON
Adds the (add frequency) value to the output frequency
OFF
Does not add the value to the output frequency
Description
Description